12
LOAD See datasheet for VitessePlus marshalling box
SUPPLY VOLTAGE 12VDC
TIME OUT PERIOD Adjustable 10 seconds to 99 minutes
LIGHT LEVEL Light to dark
FIXING METHOD Spring fixing, or surface fixing using additional Part No. MWS3A-DBB
(Surface mounting box)
MATERIAL Flame retardant ABS
TYPE Class 2
TEMPERATURE -10°C to 35°C
CONFORMITY EMC-89/336/EEC
LVD-73/23/EEC
VITP-MWS3A VitessePlus microwave presence detector
MWS3A-DBB Surface mounting box
VITP-MB VitessePlus marshalling box (non-dimming)
VITP-MBDSI VitessePlus dimming marshalling box DSI (digital dimming)
VITP-MBDALI VitessePlus dimming marshalling box DALI (digital dimming)
VITP-MBD VitessePlus dimming marshalling box 1-10V (analogue dimming)
UHS User handset with on/off override and lux up / lux down adjustment
UHS3 User handset with on/off override and cancel only
UHS3/2 User handset with off override and cancel only
DD-LCDHS IR remote control programming handset with LCD
screen
11. Specification
12. Part Numbers
LIGHTS DO NOT COME ON
Check to see if the Vitesse Plus marshalling
box is powered up and the wiring is correct.
Disconnect both RJ45 connections on the Cat
5 patch lead and re-connect, ensuring that
they ―click‖ into position, making good
connection.
Check that the ―lux hold off‖ setting is not
keeping the lights off because there is
sufficient ambient light.
If the detection range is smaller than
expected, check the diagram on page 11.
If the LED is flashing at regular intervals, this
shows that the detector is being overridden.
Press the cancel button on the handset.
LIGHTS DO NOT GO OFF
Ensure that the area is left unoccupied for
longer than the selected timer setting.
Make sure that the sensor is not adjacent to
circulating air, heaters or lamps.
If the LED is flashing at regular intervals, this
shows that the detector is being overridden
on. Press the cancel button on the handset.
10. Fault finding
Ref %WD307 Issue 2
C.P. Electronics Ltd
Brent Crescent
London
NW10 7XR
United Kingdom
Tel: + 44 (0) 333 900 0671
Fax: + 44 (0) 333 900 0674
www.cpelectronics.co.uk
enquiry@cpelectronics.co.uk
IMPORTANT NOTICE!
This device should be installed by a qualified electrician in
accordance with the latest edition of the IEE wiring regulations.
Due to our policy of continual product improvement CP Electronics reserves the right
to alter the specification of this product without prior notice.
FM 45789 EMS 534520